Is there any specific way to wire the DRIVE-CLiQ cables from devices to a Control Unit?

Important basic DRIVE-CLiQ wiring principles are listed below:

  • Ring topology is not allowed
  • Devices with the same bus speed can be daisy chained together.
  • Servo and vector drives must have separate connections.
  • TM modules must have own connection.
  • Line modules will have own connection.
  • VSM will be connected to the Line module.