Faults / Alarms

What could be causing a  return value of 8090 for DPRD_DAT/DPWR_DAT?

The hardware ID may be incorrect on the LADDR input. The required ID is the one used by the telegram - not the ID of the drive. For Startdrive, this can be found in the device view by going to Properties > General > Telegram configuration > [device name] > Start address. For drives not configured with Startdive, this can be found in the device view byhighlighting the row of the telemgra in Device overview, then navigate to Properties > General > Hardware identifier.


Getting Online

Where can I download the SINAMICS drive library from?

"The SINAMICS drive library can be downloaded from Siemens online support, using the following link:

https://support.industry.siemens.com/cs/ww/en/view/109475044
Open the SINAMICS drive library in TIA Portal to use in your projects.
This library includes SINA_INFEED, SINA_PARA, SINA_PARA_S, SINA_POS and SINA_SPEED
Contact HMK technical support for further information"

Devices and networks in TIA shows a red cross on the drive in online view. Why?

There is an error with the communication setting between the drive and PLC. This could be caused by:

- Inconsistencies in IP address and/or Profinet name in drive and PLC configuration.
- Telegrams in the PLC and drive are not configured in the same order. 